Medium-Voltage Switchgear Type NXPLUS C Wind Features & Requirements

Siemens Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C Wind up to 36 kV, Gas-Insulated.

Environmental independence

Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts
of the primary circuit under high voltage of NXPLUS C Wind switchgear

Insensitive to certain aggressive ambient conditions, such as:
– Saline air
– Air humidity
– Dust
– Condensation

Tight to ingress of foreign objects, such as:
– Dust
– Pollution
– Small animals
– Humidity

Independent of the site altitude.

Compact design

Thanks to the use of SF6 insulation, compact dimensions are possible. This is the basic prerequisite for application in wind turbines. For installation or removal, it must be possible to bring the switchgear in through the door of the wind turbine.

Maintenance-free design

Switchgear vessels designed as sealed pressure systems, maintenance-free switching devices and enclosed cable plugs ensure:
• Maximum supply reliability
• Personnel safety
•  Sealed-for-life design according to IEC 62271-200 (sealed pressure system)
•  Installation, operation, extension and replacement without SF6 gas work
• Reduced operating costs
• Cost-efficient investment
• No maintenance cycles.

Innovation

The use of digital secondary systems and combined protection and control devices ensures:

Service life

Under normal operating conditions, the expected service life of the gas-insulated switchgear NXPLUS C Wind is at least 35 years, probably 40 to 50 years, taking the tightness of the hermetically welded switchgear vessel into account. The service life is limited by the maximum number of operating cycles of the switching devices installed:

Personal safety

Security of operation

General

Interlocks

•  According to IEC 62271-200 and VDE 0671-200
• Logical mechanical interlocks prevent maloperation
•  Three-position disconnector can only be operated with circuit-breaker in OPEN position
•  Circuit-breaker can only be operated with three-position switch in end position and operating lever removed
•  Three-position disconnector interlocked against the circuit-breaker in circuit-breaker panels
•  “Feeder earthed“ locking device
•  Locking device for three-position switch

The following interlocks can be fulfilled by placing the padlock accordingly:

Padlock on the left: Three-position switch “DISCONNECTING” function cannot be operated, three-position switch “READY-TO-EARTH” function can be operated

Padlock in the center: Control gate blocked, no switching operations possible

Padlock on the right: Three-position switch “DISCONNECTING” function can be operated, three-position switch “READY-TO-EARTH” function cannot be operated

Option: Cable compartment cover interlocked against the three-position switch (circuit-breaker panel, disconnector panel, ring-main panel)

Option: Electromagnetic interlocks

Option: Actuating openings can be padlocked

Option: “Feeder earthed“ locking device.

Modular design

Instrument transformers

Vacuum circuit-breaker

Secondary systems

Standards

Switchgear installation options

For single-busbar applications:

– Wall-standing arrangement or

– Free-standing arrangement.

Room height
≥ 2400 mm all switchgear assemblies without busbar voltage transformer
≥ 2700 mm all switchgear assemblies with busbar voltage transformer

Door dimensions: The door dimensions depend on the dimensions of the individual panels (see page 11 of full manual).

Switchgear fixing

Transport

NXPLUS C Wind switchgear is delivered in form of individual panels, or as a panel combination with a maximum width of 1500 mm. Please observe the following:
•  Transport facilities on site
•  Transport dimensions and transport weights
•  During the transport of panel groups, the corresponding transport rods must be used
•  Size of door openings in building.

Packing

Means of transport: Rail and truck
– Panels on pallets
– Open packing with PE protective foil.

Means of transport: Ship
– Panels on pallets
– In closed crates with sealed upper and lower PE protective foil
– With desiccant bags
– With sealed wooden base
– Max. storage time: 6 months.

Means of transport: Container
– Panels on pallets
– With sealed upper and lower PE protective foil
– With desiccant bags.

Means of transport: Airplane
– Panels on pallets
– In wooden latticed crate with sealed upper and lower PE protective foil
– With desiccant bags.

Complete technical catalogue is available at Siemens Website.