Cable Capacity
- For Cu Wire Current Capacity (Up to 30 Sq.mm) = 6X Size of Wire in Sq.mm
- Ex. For 2.5 Sq.mm=6×2.5=15 Amp, For 1 Sq.mm=6×1=6 Amp, For 1.5 Sq.mm=6×1.5=9 Amp
- For Cable Current Capacity = 4X Size of Cable in Sq.mm ,Ex. For 2.5 Sq.mm=4×2.5=9 Amp.
- Nomenclature for cable Rating = Uo/U
- where Uo=Phase-Ground Voltage, U=Phase-Phase Voltage, Um=Highest Permissible Voltage
Current Capacity of Equipment’s:
- 1 Phase Motor draws Current=7Amp per HP.
- 3 Phase Motor draws Current=1.25Amp per HP.
- Full Load Current of 3 Phase Motor=HPx1.5
- Full Load Current of 1 Phase Motor=HPx6
- No Load Current of 3 Phase Motor =30% of FLC
- KW Rating of Motor=HPx0.75
- Full Load Current of equipment =1.39xKVA (for 3 Phase 415Volt)
- Full Load Current of equipment =1.74xKw (for 3 Phase 415Volt)
Earthing Resistance:
- Earthing Resistance for Single Pit=5Ω ,Earthing Grid=0.5Ω
- As per NEC 1985 Earthing Resistance should be <5Ω.
- Voltage between Neutral and Earth <=2 Volts
- Resistance between Neutral and Earth <=1Ω
- Creepage Distance=18 to 22mm/KV (Moderate Polluted Air) or
- Creepage Distance=25 to 33mm/KV (Highly Polluted Air)
Minimum Bending Radius:
- Minimum Bending Radius for LT Power Cable=12xDia of Cable.
- Minimum Bending Radius for HT Power Cable=20xDia of Cable.
- Minimum Bending Radius for Control Cable=10xDia of Cable.
Insulation Resistance:
- Insulation Resistance Value for Rotating Machine= (KV+1) MΩ.
- Insulation Resistance Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
- Insulation Resistance Value for Equipment (<1KV) = Minimum 1 MΩ.
- Insulation Resistance Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
- Insulation Resistance Value for Panel = 2 x KV rating of the panel.
- Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
- Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
- Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
- Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
- Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting Arrestor:
- Arrestor have Two Rating=
- (1) MCOV=Max. Continuous Line to Ground Operating Voltage.
- (2) Duty Cycle Voltage. (Duty Cycle Voltage>MCOV).
Transformer:
- Current Rating of Transformer=KVAx1.4
- Short Circuit Current of T.C /Generator= Current Rating / % Impedance
- No Load Current of Transformer=<2% of Transformer Rated current
- Capacitor Current (Ic)=KVAR / 1.732xVolt (Phase-Phase)
- Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
- Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
- The diversity they would apply to apartments is around 60%
- Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
- 4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
- Clearances, approx.1000mm around TC allow for transformer movement for replacement.
Diesel Generator:
- Diesel Generator Set Produces=3.87 Units (KWH) in 1 Litter of Diesel.
- Requirement Area of Diesel Generator = for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
- DG less than or equal to 1000kVA must be in a canopy.
- DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room
- DG noise levels to be less than 75dBA @ 1meter.
- DG fuel storage tanks should be a maximum of 990 Litter per unit Storage tanks above this level will trigger more stringent explosion protection provision.
Current Transformer:
- Nomenclature: CT
- Ratio: input / output current ratio
- Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
- Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
- Accuracy Limit Factor:
- Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10 (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
- As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accurate to 0.3 percent if the connected secondary burden if impedance does not exceed 0.1 ohms.
- As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).
Size of Capacitor for P.F Correction:
For Motor |
|
Size of Capacitor = 1/3 Hp of Motor ( 0.12x KW of Motor) | |
For Transformer |
|
< 315 KVA | 5% of KVA Rating |
315 KVA to 1000 KVA | 6% of KVA Rating |
>1000 KVA | 8% of KVA Rating |
Earthing Resistance value:
Earthing Resistance Value |
|
Power Station | 0.5 Ω |
Sub Station Major | 1.0 Ω |
Sub Station Minor | 2.0 Ω |
Distribution Transformer | 5.0 Ω |
Transmission Line | 10 Ω |
Single Isolate Earth Pit | 5.0 Ω |
Earthing Grid | 0.5 Ω |
As per NEC Earthing Resistance should be <5.0 Ω |
Voltage Limit (As per CPWD & Kerala Elect.Board):
Voltage Limit (As Per CPWD) |
|
240V | < 5 KW |
415V | <100 KVA |
11KV | MVA |
22KV | <6 MVA |
33KV | <12 MVA |
66KV | <20 MVA |
110KV | <40 MVA |
220KV | >40 MVA |
Voltage Variation
> 33 KV | (-) 12.5% to (+) 10% |
< 33 KV | (-) 9% to (+) 6% |
Low Voltage | (-) 6% to (+) 6% |
Insulation Class:
Insulation |
Temperature |
Class A |
105°C |
Class E |
120°C |
Class B |
130°C |
Class F |
155°C |
Class H |
180°C |
Class N |
200°C |
Standard Voltage Limit:
Voltage | IEC (60038) | IEC (6100:3.6) | Indian Elect. Rule |
ELV | < 50 V | ||
LV | 50 V to 1 KV | <=1 KV | < 250 V |
MV | <= 35 KV | 250 V to 650 V | |
HV | > 1KV | <= 230 KV | 650 V to 33 KV |
EHV | > 230 KV | > 33 KV |
Standard Electrical Connection (As per GERC):
As per Type of Connection |
|
Connection |
Voltage |
LT Connection |
<=440V |
HT connection |
440V to 66KV |
EHT connection |
>= 66KV |
As per Electrical Load Demand |
|
Up 6W Load demand |
1 Phase 230V Supply |
6W to 100KVA(100KW) |
3 Phase 440V Supply |
100KVA to 2500KVA |
11KV,22KV,33KV |
Above 2500KVA |
66KV |
HT Connection Earthing |
|
H.T Connection’s Earthing Strip |
20mmX4mm Cu. Strip |
CT & PT bodies |
2Nos |
PT Secondary |
1Nos |
CT Secondary |
1Nos |
I/C and O/G Cable+ Cubicle Body |
2Nos |
Standard Meter Room Size (As per GERC):
Meter Box Height | Upper level does not beyond 1.7 meter and Lower level should not below 1.2 meter from ground. |
Facing of Meter Box | Meter Box should be at front area of Building at Ground Floor. |
Meter Room / Closed Shade | 4 meter square Size |
Approximate Load as per Sq.ft Area (As per DHBVN):
Sq.ft Area | Required Load (Connected) |
< 900 Sq.ft | 8 KW |
901 Sq.ft to 1600 Sq.ft | 16 KW |
1601 Sq.ft to 2500 Sq.ft | 20 KW |
> 2500 Sq.ft | 24 KW |
For Flats :100 Sq.ft / 1 KW | |
For Flats USS /TC: 100 Sq.ft / 23 KVA |
Contracted Load in case of High-rise Building:
For Domestic Load | 500 watt per 100 Sq. foot of the constructed area. |
For Commercial | 1500 watt per 100 Sq. foot of the constructed area |
Other Common Load | For lift, water lifting pump, streetlight if any, corridor/campus lighting and other common facilities, actual load shall be calculated |
Staircase Light | 11KW/Flat Ex: 200Flat=200×11=2.2KW |
Sanctioned Load for Building |
|
Up to 50 kW | The L.T. existing mains shall be strengthened. |
50 kW to 450 kW (500 kVA) | 11 kV existing feeders shall be extended if spare capacity is available otherwise, new 11 kV feeders shall be constructed. |
450 kW to 2550 kW (3000 kVA) | 11 kV feeder shall be constructed from the nearest 33 kV or 110 kV substation |
2550 kW to 8500 kW (10,000 kVA) | 33kV feeder from 33 kV or 110 kV sub station |
8500 kW (10,000 kVA) | 110 kV feeder from nearest 110 kV or 220 kV sub-station |
Sub Station Capacity & Short Circuit Current Capacity:
As per GERC |
||
Voltage | Sub Station Capacity | Short Circuit Current |
400 KV | Up to 1000 MVA | 40 KA (1 to 3 Sec) |
220 KV | Up to 320 MVA | 40 KA (1 to 3 Sec) |
132 KV | Up to 150 MVA | 32 KA (1 to 3 Sec) |
66 KV | Up to 80 MVA | 25 KA (1 to 3 Sec) |
33 KV | 1.5 MVA to 5 MVA | 35 KA (Urban) (1 to 3 Sec) |
11 KV | 150 KVA to 1.5 MVA | 25 KA (Rural) (1 to 3 Sec) |
415 V | 6 KVA to 150 KVA | 10 KA (1 to 3 Sec) |
220 V | Up to 6 KVA | 6 KA (1 to 3 Sec) |
Sub Station Capacity & Short Circuit Current Capacity:
As per Central Electricity Authority |
||
Voltage | Sub Station Capacity | Short Circuit Current |
765 KV |
4500 MVA |
31.5 KA for 1 Sec |
400 KV |
1500 MVA |
31.5 KA for 1 Sec |
220 KV |
500 MVA |
40 KA for 1 Sec |
110/132 KV |
150 MVA |
40 KA or 50 KA for 1 Sec |
66 KV |
75 MVA |
40 KA or 50 KA for 1 Sec |
Minimum Ground Clearance and Fault Clearing Time:
Voltage | Min. Ground Clearance | Fault Clear Time |
400 KV | 8.8 Meter | 100 mille second |
220 KV | 8.0 Meter | 120 mille second |
132 KV | 6.1 Meter | 160 mille second |
66 KV | 5.1 Meter | 300 mille second |
33 KV | 3.7 Meter | |
11 KV | 2.7 Meter |
Bus bar Ampere Rating:
For Phase Bus bar | Aluminium 130 Amp / Sq.cm or 800Amp / Sq.inch. |
For Phase Bus bar | Copper 160 Amp / Sq.cm or 1000Amp / Sq.inch |
For Neutral Bus bar | Same as Phase Bus bar up to 200 Amp than Size of Neutral Bus bar is at least half of Phase Bus bar. |
Bus bar Spacing:
Between Phase and Earth | 26mm (Min) |
Between Phase and Phase | 32mm (Min) |
Bus bar Support between Two Insulator | 250mm. |
Sound Level of Diesel Generator (ANSI 89.2&NEMA 51.20):
KVA |
Max. Sound Level |
<9 KVA | 40 DB |
10 KVA to 50 KVA | 45 DB |
51 KVA to 150 KVA | 50 DB |
151 KVA to 300 KVA | 55 DB |
301 KVA to 500 KVA | 60 DB |
IR Value of Transformer:
IR Value of Transformer |
|||
Voltage |
30°C |
40°C |
50°C |
>66KV |
600MΩ |
300MΩ |
150MΩ |
22KV to 33KV |
500MΩ |
250MΩ |
125MΩ |
6.6KV to 11KV |
400MΩ |
200MΩ |
100MΩ |
<6.6KV |
200MΩ |
100MΩ |
50MΩ |
415V |
100MΩ |
50MΩ |
20MΩ |
Standard Size of MCB/MCCB/ELCB/RCCB/SFU/Fuse:
MCB | Up to 63 Amp (80Amp and 100 Amp a per Request) |
MCCB | Up to 1600 Amp (2000 Amp as per Request) |
ACB | Above 1000 Amp |
MCB Rating | 6A,10A,16A,20A,32A,40A,50A,63A |
MCCB Rating | 0.5A,1A,2A,4A,6A,10A,16A,20A,32A,40A,50A,63A,80A,100A (Domestic Max 6A) |
RCCB/ELCB | 6A,10A,16A,20A,32A,40A,50A,63A,80A,100A |
Sen. of ELCB | 30ma (Domestic),100ma (Industrial),300ma |
DPIC (Double Pole Iron Clad) main switch | 5A,15A,30 A for 250V |
TPIC (Triple Pole Iron Clad) main switch | 30A, 60A, 100A, 200 A For 500 V |
DPMCB | 5A, 10A, 16A, 32A and 63 A for 250V |
TPMCCB | 100A,200A, 300Aand 500 A For 660 V |
TPN main switch | 30A, 60A, 100A, 200A, 300 A For 500 V |
TPNMCB | 16A, 32A,63A For 500 V, beyond this TPNMCCB: 100A, 200A, 300A, 500 A For 660 V |
TPN Fuse Unit (Rewirable) | 16A,32A,63A,100A,200A |
Change over switch (Off Load) | 32A,63A,100A,200A,300A,400A,630A,800A |
SFU (Switch Fuse Unit) | 32A,63A,100A,125A,160A,200A,250A,315A,400A,630A |
HRC Fuse TPN (Bakelite) | 125A,160A,200A,250A,400A.630A |
HRC Fuse DPN (Bakelite) | 16A,32A,63A |
MCB/MCCB/ELCB Termination Wire / Cable |
|
Up to 20A MCB | Max. 25 Sq.mm |
20A to 63A MCB | Max. 35 Sq.mm |
MCCB | Max. 25 Sq.mm |
6A to 45A ELCB | 16 Sq.mm |
24A to 63A ELCB | 35 Sq.mm |
80A to 100A ELCB | 50 Sq.mm |
Transformer Earthing Wire / Strip Size:
Size of T.C or DG |
Body Earthing |
Neutral Earthing |
<315 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 25×3 mm Cu Strip |
315 KVA to 500 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 25×3 mm Cu Strip |
500 KVA to 750 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 40×3 mm Cu Strip |
750 KVA to 1000 KVA | 25×3 mm Cu / 40×6 mm GI Strip | 50×3 mm Cu Strip |
Motor Earthing Wire / Strip Size:
Size of Motor |
Body Earthing |
< 5.5 KW |
85 SWG GI Wire |
5.5 KW to 22 KW |
25×6 mm GI Strip |
22 KW to 55 KW |
40×6 mm GI Strip |
>55 KW |
50×6 mm GI Strip |
Panel Earthing Wire / Strip Size:
Type of Panel |
Body Earthing |
Lighting & Local Panel |
25×6 mm GI Strip |
Control & Relay Panel |
25×6 mm GI Strip |
D.G & Exciter Panel |
50×6 mm GI Strip |
D.G & T/C Neutral |
50×6 mm Cu Strip |
Electrical Equipment Earthing:
Equipment |
Body Earthing |
LA (5KA,9KA) |
25×3 mm Cu Strip |
HT Switchgear |
50×6 mm GI Strip |
Structure |
50×6 mm GI Strip |
Cable Tray |
50×6 mm GI Strip |
Fence / Rail Gate |
50×6 mm GI Strip |
Earthing Wire (As per BS 7671)
Cross Section Area of Phase, Neutral Conductor(S) mm2 |
Minimum Cross Section area of Earthing Conductor (mm2) |
S<=16 |
S (Not less than 2.5 mm2) |
16<S<=35 |
16 |
S>35 |
S/2 |
Area for Transformer Room: (As per NBC-2005):
Transformer Size | Min. Transformer Room Area (M2) | Min. Total Sub Station Area( Incoming HV,LV Panel, T.C Roof) (M2) | Min. Space Width (Meter) |
1X160 |
14 |
90 |
9 |
2X160 |
28 |
118 |
13.5 |
1X250 |
15 |
91 |
9 |
2X250 |
30 |
121 |
13.5 |
1X400 |
16.5 |
93 |
9 |
2X400 |
33 |
125 |
13.5 |
3X400 |
49.5 |
167 |
18 |
2X500 |
36 |
130 |
14.5 |
3X500 |
54 |
172 |
19 |
2X630 |
36 |
132 |
14.5 |
3X630 |
54 |
176 |
19 |
2X800 |
39 |
135 |
14.5 |
3X800 |
58 |
181 |
14 |
2X1000 |
39 |
149 |
14.5 |
3X1000 |
58 |
197 |
19 |
- The Capacitor Bank should be automatic Switched type for Sub Station of 5MVA and Higher.
- Transformer up to 25KVA can be mounted direct on Pole.
- Transformer from 25KVA to 250KVA can be mounted either on “H” Frame of Plinth.
- Transformer above 250KVA can be mounted Plinth only.
- Transformer above 100MVA shall be protected by Drop out Fuse or Circuit Breaker.
Span of Transmission Line (Central Electricity Authority):
Voltage |
Normal Span |
765 KV |
400 to 450 Meter |
400 KV |
400 Meter |
220 KV |
335,350,375 Meter |
132 KV |
315,325,335 Meter |
66 KV |
240,250,275 Meter |
Max. Lock Rotor Amp for 1 Phase 230 V Motor (NEMA)
HP |
Amp |
1 HP |
45 Amp |
1.5 HP |
50 Amp |
2 HP |
65 Amp |
3 HP |
90 Amp |
5 HP |
135 Amp |
7.5 HP |
200 Amp |
10 HP |
260 Amp |
Three Phase Motor Code (NEMA)
HP |
Code |
<1 HP |
L |
1.5 to 2.0 HP |
L,M |
3 HP |
K |
5 HP |
J |
7 to 10 HPPHPHPHHHHH |
H |
>15 HP |
G |
Service Factor of Motor:
HP |
Synchronous Speed (RPM) |
||||||
3600 RPM |
1800 RPM |
1200 RPM |
900 RPM |
720 RPM |
600 RPM |
514 RPM |
|
1 HP |
1.25 |
1.15 |
1.15 |
1.15 |
1 |
1 |
1 |
1.5 to 1.25 HP |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
150 HP |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
1 |
200 HP |
1.15 |
1.15 |
1.15 |
1.15 |
1.15 |
1 |
1 |
> 200 HP |
1 |
1.15 |
1 |
1 |
1 |
1 |
1 |
Type of Contactor:
Type |
Application |
AC1 |
Non Inductive Load or Slightly Inductive Load |
AC2 |
Slip Ring Motor, Starting, Switching OFF |
AC3 |
Squirrel Cage Motor |
AC4,AC5,AC5a, AC5b,AC6a |
Rapid Start & Rapid Stop |
AC 5a |
Auxiliary Control circuit |
AC 5b |
Electrical discharge Lamp |
AC 6a |
Electrical Incandescent Lamp |
AC 6b |
Transformer Switching |
AC 7a |
Switching of Capacitor Bank |
AC 7b |
Slightly Inductive Load in Household |
AC 5a |
Motor Load in Household |
AC 8a |
Hermetic refrigerant compressor motor with Manual Reset O/L Relay |
AC 8b |
Hermetic refrigerant compressor motor with Automatic Reset O/L Relay |
AC 12 |
Control of Resistive Load & Solid State Load |
AC 13 |
Control of Resistive Load & Solid State Load with Transformer Isolation |
AC 14 |
Control of small Electro Magnetic Load (<72 VA) |
AC 15 |
Control of Electro Magnetic Load (>72 VA) |
Contactor Coil:
Coil Voltage |
Suffix |
24 Volt |
T |
48 Volt |
W |
110 to 127 Volt |
A |
220 to 240 Volt |
B |
277 Volt |
H |
380 to 415 Volt |
L |
Overhead Conductor /Cable Size:
Voltage |
Overhead Conductor |
Cable Size |
33 KV | ACSR-Panther/Wolf/Dog , AAAC | 150,185,300,400,240 mm2 Cable |
11 KV | ACSR-Dog/Recon/Rabbit , AAAC | 120, 150,185,300 mm2 Cable |
LT | ACSR-Dog/Recon/Rabbit , AAC,AAAC | 95,120, 150,185,300 mm2 Cable |
Transmission / Distribution Line:
Span |
Height of Tower |
400KV=400 Meter |
400KV=30Meter (Base 8.8 Meter) |
220KV=350 Meter |
220KV=23Meter (Base 5.2 Meter) |
132KV=335 Meter |
220KV Double Circuit=28 Meter |
66KV=210 Meter |
66KV=13Meter |
Conductor Ampere |
Voltage wise Conductor |
Dog=300Amp |
400KV=Moose ACSR=500MVA Load |
Panther=514Amp |
220KV=Zebra ACSR=200MVA Load |
Zebra=720Amp |
132KV=Panther ACSR=75MVA Load |
Rabbit=208Amp |
66KV=Dog ACSR=50MVA Load |
Moose=218Amp |
Type of Tower:
Type |
Used |
Angle/Deviation |
A |
Suspension Tower | Up to 2° |
B |
Small Angle Tower | 2° to 15° |
C |
Medium Angle Tower | 15° to 30° |
D |
Large Angle / Dead End Tower | 30° to 60° & Dead End |
Tower Swing Angle Clearance (Metal Part to Live Part):
Swing Angle |
Live Part to Metal Part Clearance (mm) |
|||
66KV |
132KV |
220KV |
400KV |
|
0° |
915mm |
1530mm |
2130mm |
3050mm |
15° |
915mm |
1530mm |
2130mm |
– |
22° |
– |
– |
– |
3050mm |
30° |
760mm |
1370mm |
1830mm |
– |
44° |
– |
– |
– |
1860mm |
44° |
610mm |
1220mm |
1675mm |
– |
Cable Coding (IS 1554) ???? A2XFY / FRLS / FRPVC / FRLA / PILC)
A |
Aluminium |
2X |
XLPE |
F |
Flat Armoured |
W |
Wire Armoured |
Y |
Outer PVC Insulation Sheath |
W |
Steel Round Wire |
WW |
Steel double round wire Armoured |
YY |
Steel double Strip Armoured |
FR |
Fire Retardation |
LS |
Low Smoke |
LA |
Low Acid Gas Emission |
WA |
Non Magnetic round wire Armoured |
FA |
Non Magnetic Flat wire Armoured |
FF |
Double Steel Round Wire Armoured |
Corona Ring Size:
Voltage |
Size |
<170 KV | 160mm Ring put at HV end |
>170 KV | 350mm Ring put at HV end |
>275 KV | 450mm Ring put at HV end & 350 mm Ring put at Earth end |
Load as per Sq.Ft:
Type of Load |
Load/Sq.Ft |
Diversity Factor |
Industrial |
1000 Watt/Sq.Ft |
0.5 |
Commercial |
30 Watt/Sq.Ft |
0.8 |
Domestic |
15 Watt/Sq.Ft |
0.4 |
Lighting |
15 Watt/Sq.Ft |
0.8 |
Size of Ventilation Shaft:
Height of Building in meter | Size of ventilation shaft in sq meter | Minimum size of shaft in meter |
9.0 |
1.5 |
1.0 |
12.5 |
3.0 |
1.2 |
15 and above |
4.0 |
1.5 |
Accuracy Class of Metering CT:
Metering Class CT |
|
Class | Applications |
0.1 To 0.2 | Precision measurements |
0.5 | High grade kilowatt hour meters for commercial grade kilowatt hour meters |
3 | General industrial measurements |
3 OR 5 | Approximate measurements |
Accuracy Class Letter of CT:
Metering Class CT |
|
Accuracy Class | Applications |
B |
Metering Purpose |
Protection Class CT |
|
C |
CT has low leakage flux. |
T |
CT can have significant leakage flux. |
H |
CT accuracy is applicable within the entire range of secondary currents from 5 to 20 times the nominal CT rating. (Typically wound CTs.) |
L |
CT accuracy applies at the maximum rated secondary burden at 20 time rated only. The ratio accuracy can be up to four times greater than the listed value, depending on connected burden and fault current. (Typically window, busing, or bar-type CTs.) |
Accuracy Class of Protection CT:
Class | Applications |
10P5 | Instantaneous over current relays & trip coils: 2.5VA |
10P10 | Thermal inverse time relays: 7.5VA |
10P10 | Low consumption Relay: 2.5VA |
10P10/5 | Inverse definite min. time relays (IDMT) over current |
10P10 | IDMT Earth fault relays with approximate time grading:15VA |
5P10 | IDMT Earth fault relays with phase fault stability or accurate time grading: 15VA |
Electrical Useful Equations
- For Sinusoidal Current : Form Factor = RMS Value/Average Value=1.11
- For Sinusoidal Current : Peak Factor = Max Value/RMS Value =1.414
- Average Value of Sinusoidal Current(Iav)=0.637xIm (Im= Max.Value)
- RMS Value of Sinusoidal Current(Irms)=0.707xIm (Im= Max.Value)
- A.C Current=D.C Current/0.636.
- Phase Difference between Phase= 360/ No of Phase (1 Phase=230/1=360°,2Phase=360/2=180°)
- Short Circuit Level of Cable in KA (Isc)=(0.094xCable Dia in Sq.mm)/√ Short Circuit Time (Sec)
- Max.Cross Section Area of Earthing Strip(mm2) =√(Fault Current x Fault Current x Operating Time of Disconnected Device ) / K
- K=Material Factor, K for Cu=159, K for Alu=105, K for steel=58 , K for GI=80
- Most Economical Voltage at given Distance=5.5x√ ((km/1.6)+(kw/100))
- Cable Voltage Drop(%)=(1.732xcurrentx(RcosǾ+jsinǾ)x1.732xLength (km)x100)/(Volt(L-L)x Cable Run.
- Spacing of Conductor in Transmission Line (mm) = 500 + 18x (P-P Volt) + (2x (Span in Length)/50).
- Protection radius of Lighting Arrestor = √hx (2D-h) + (2D+L). Where h= height of L.A, D-distance of equipment (20, 40, 60 Meter), L=Vxt (V=1m/ms, t=Discharge Time).
- Size of Lighting Arrestor= 1.5x Phase to Earth Voltage or 1.5x (System Voltage/1.732).
- Maximum Voltage of the System= 1.1xRated Voltage (Ex. 66KV=1.1×66=72.6KV)
- Load Factor=Average Power/Peak Power
- If Load Factor is 1 or 100% = This is best situation for System and Consumer both.
- If Load Factor is Low (0 or 25%) =you are paying maximum amount of KWH consumption. Load Factor may be increased by switching or use of your Electrical Application.
- Demand Factor= Maximum Demand / Total Connected Load (Demand Factor <1)
- Demand factor should be applied for Group Load
- Diversity Factor= Sum of Maximum Power Demand / Maximum Demand (Demand Factor >1)
- Diversity factor should be consider for individual Load
- Plant Factor(Plant Capacity)= Average Load / Capacity of Plant
- Fusing Factor=Minimum Fusing Current / Current Rating (Fusing Factor>1).
- Voltage Variation(1 to 1.5%)= ((Average Voltage-Min Voltage)x100)/Average Voltage
- Ex: 462V, 463V, 455V, Voltage Variation= ((460-455) x100)/455=1.1%.
- Current Variation(10%)= ((Average Current-Min Current)x100)/Average Current
- Ex:30A,35A,30A, Current Variation=((35-31.7)x100)/31.7=10.4%
- Fault Level at TC Secondary=TC (VA) x100 / Transformer Secondary (V) x Impedance (%)
- Motor Full Load Current= Kw /1.732xKVxP.FxEfficiency